SERVICE PACKAGES

Services

Monthly Inspection

As per CSA Standards (C282-15 Clause 11.4 – table 3) during a monthly inspection a simulation of a failure of the normal electrical supply and operation of the system under at least 30% of the rated load for 60 minutes must be performed. Also required is the operation of all automatic transfer switches under load [if more than one], inspection for sparking and for bearing seal leakage. In addition, draining of the exhaust system condensation trap is required.

The person performing the monthly inspection should also inspect for correct operation of all auxiliary equipment that includes radiator shutter control, coolant pumps, fuel transfer pumps, oil coolers, and engine room ventilation system(s) and record all inspections, tests and corrective actions in the log.